磁导航1.0内部交管和信号交互

This commit is contained in:
ykkokluo
2026-08-24 14:55:35 +08:00
parent cacc5fea5c
commit 244b0af6c8
60 changed files with 6395 additions and 294 deletions
+199 -64
View File
@@ -1,4 +1,6 @@
using System;
using System.Collections.Generic;
using System.Linq;
using System.Threading;
using SimpleCore.Library;
using StandardScene.Signal.Model;
@@ -6,41 +8,43 @@ using StandardScene.Signal.Model;
namespace StandardScene.Signal.Plc
{
/// <summary>
/// 单机构 200ms 循环:心跳、读允许进出、回读写值、按需写入、自动离站。
/// 对齐反编译 <c>PLCManager.ExcuteThreadMethod</c>。
/// 单机构 200ms 循环:心跳、按工位读 BOOL(或旧一字节)、回写变化位、自动离站。
/// </summary>
/// <remarks>
/// 一拍顺序固定,失败则本拍标断线并 return,避免用脏数据推进状态机:
/// 1. 翻转内存心跳标志;若配置了 HeartDb,读当前位再写反码(PLC 侧看翻转判断调度活着)。
/// 2. 读 ReadDb → <see cref="PlcStationRuntime.ReadSignal"/>。
/// 3. 回读 WriteDb → ReadWriteSignal;与目标 WriteSignal 一致则 WriteSuccess=true。
/// 4. 目标与回读不一致且尚未成功时写入目标字节。
/// 5. <see cref="PlcStationLogic.AutoLeave"/>。
/// 读写均在 <see cref="PlcStationRuntime.Sync"/> 内,与扫车 Handler 互斥。
/// </remarks>
public sealed class PlcStationWorker : IDisposable
{
private readonly SiemensPlcSession _session;
private readonly int _pollMs;
private readonly Action _onTick;
private readonly PlcStationModel _station;
private readonly List<PlcStationRuntime> _docks;
private CancellationTokenSource _cts;
private Thread _thread;
/// <summary>断线日志节流起点,避免 200ms 打满诊断。</summary>
private DateTime _lastFailLog = DateTime.MinValue;
public PlcStationWorker(PlcStationRuntime runtime, SiemensPlcSession session, int pollMs, Action onTick = null)
public PlcStationWorker(
PlcStationModel station,
IEnumerable<PlcStationRuntime> docks,
SiemensPlcSession session,
object sync,
int pollMs,
Action onTick = null)
{
Runtime = runtime ?? throw new ArgumentNullException(nameof(runtime));
_station = station ?? throw new ArgumentNullException(nameof(station));
_docks = (docks ?? Array.Empty<PlcStationRuntime>()).Where(d => d != null).ToList();
_session = session ?? throw new ArgumentNullException(nameof(session));
Sync = sync ?? new object();
_pollMs = Math.Max(50, pollMs);
_onTick = onTick;
foreach (var d in _docks)
d.Heart = false;
}
/// <summary>本机构运行态,扫车线程按 JgName 查找后加 Sync 读写。</summary>
public PlcStationRuntime Runtime { get; }
public object Sync { get; }
public IReadOnlyList<PlcStationRuntime> Docks => _docks;
public PlcStationRuntime Runtime => _docks.Count > 0 ? _docks[0] : null;
/// <summary>启动后台线程。重复 Start 若仍存活则忽略。</summary>
public void Start()
{
if (_thread != null && _thread.IsAlive) return;
@@ -48,13 +52,12 @@ namespace StandardScene.Signal.Plc
_thread = new Thread(Loop)
{
IsBackground = true,
Name = $"PlcStation:{Runtime.Config.JgName}"
Name = $"PlcStation:{_station.JgName}"
};
_thread.Start();
Diagnosis.Log($"{Runtime.Config.JgName} Worker 已启动 → {Runtime.Config.Ip}:{Runtime.Config.Port}", "PLC", true);
Diagnosis.Log($"{_station.JgName} Worker 已启动 → {_station.Ip}:{_station.Port} 工位{_docks.Count}", "PLC", true);
}
/// <summary>取消循环、最多等 2s、关闭 S7 连接并标断线。</summary>
public void Stop()
{
try { _cts?.Cancel(); }
@@ -63,8 +66,9 @@ namespace StandardScene.Signal.Plc
catch { }
_thread = null;
_session.Close();
Runtime.IsConnected = false;
Diagnosis.Log($"{Runtime.Config.JgName} Worker 已停止", "PLC", true);
foreach (var d in _docks)
d.IsConnected = false;
Diagnosis.Log($"{_station.JgName} Worker 已停止", "PLC", true);
}
public void Dispose() => Stop();
@@ -76,14 +80,17 @@ namespace StandardScene.Signal.Plc
{
try
{
lock (Runtime.Sync)
lock (Sync)
Tick();
}
catch (Exception ex)
{
Runtime.LastError = ex.Message;
Runtime.IsConnected = false;
LogFail($"{Runtime.Config.JgName} 周期异常 {ex.Message}");
foreach (var d in _docks)
{
d.LastError = ex.Message;
d.IsConnected = false;
}
LogFail($"{_station.JgName} 周期异常 {ex.Message}");
}
try { _onTick?.Invoke(); }
@@ -94,17 +101,18 @@ namespace StandardScene.Signal.Plc
}
}
/// <summary>单拍 PLC 交互。心跳地址为空则跳过心跳;读写地址为空则跳过对应步骤。</summary>
internal void Tick()
{
var cfg = Runtime.Config;
Runtime.Heart = !Runtime.Heart;
var heart = !_docks.Select(d => d.Heart).FirstOrDefault();
foreach (var d in _docks)
d.Heart = heart;
if (!string.IsNullOrWhiteSpace(cfg.HeartDb))
var heartAddr = PlcConfigLoader.ResolveHeartAddress(_station);
if (!string.IsNullOrWhiteSpace(heartAddr))
{
if (_session.TryReadBool(cfg.HeartDb, out var bit))
if (_session.TryReadBool(heartAddr, out var bit))
{
_session.TryWriteBool(cfg.HeartDb, !bit);
_session.TryWriteBool(heartAddr, !bit);
Thread.Sleep(20);
}
else
@@ -114,56 +122,183 @@ namespace StandardScene.Signal.Plc
}
}
var boolDocks = _docks.Where(d => !d.Dock.UseByteIo).ToList();
var byteDocks = _docks.Where(d => d.Dock.UseByteIo).ToList();
if (boolDocks.Count > 0 && !TickBoolDocks(boolDocks))
return;
foreach (var rt in byteDocks)
{
if (!TickByteDock(rt))
return;
}
foreach (var rt in _docks)
{
rt.IsConnected = true;
rt.LastError = "";
PlcStationLogic.AutoLeave(rt);
}
}
private bool TickBoolDocks(List<PlcStationRuntime> docks)
{
var db = PlcConfigLoader.ResolveDb(_station);
var bytes = new List<int>();
foreach (var rt in docks)
CollectBytes(rt.Dock, bytes);
if (bytes.Count == 0)
return true;
var origin = bytes.Min();
var last = bytes.Max();
var len = (ushort)(last - origin + 1);
if (!_session.TryReadBytes(PlcAddress.Byte(db, origin), len, out var buffer) ||
buffer == null || buffer.Length < len)
{
MarkDisconnected("BOOL 块读失败");
return false;
}
var changedBytes = new HashSet<int>();
foreach (var rt in docks)
{
var dock = rt.Dock;
var allowIn = PlcAddress.GetBit(buffer, origin, dock.AllowInByte, dock.AllowInBit);
var allowOut = PlcAddress.GetBit(buffer, origin, dock.AllowOutByte, dock.AllowOutBit);
rt.ReadSignal = allowIn
? SignalReadValue.
: allowOut
? SignalReadValue.
: SignalReadValue.;
var readWrite = DecodeWrite(buffer, origin, dock);
rt.ReadWriteSignal = readWrite;
if (readWrite == rt.WriteSignal)
rt.WriteSuccess = true;
if (rt.WriteSignal != readWrite && !rt.WriteSuccess)
{
Diagnosis.Log(
$"AGV→机构 {rt.DisplayName} 写入【{rt.WriteSignal}】请求进入{rt.RequestInAgvNo} 到达{rt.InAgvNo}",
"JGControl", true);
EncodeWrite(buffer, origin, dock, rt.WriteSignal, changedBytes);
}
}
foreach (var abs in changedBytes)
{
var i = abs - origin;
if (i < 0 || i >= buffer.Length)
continue;
if (!_session.TryWriteByte(PlcAddress.Byte(db, abs), buffer[i]))
{
MarkDisconnected("BOOL 写失败");
return false;
}
}
return true;
}
private bool TickByteDock(PlcStationRuntime rt)
{
var cfg = rt.Dock;
if (!string.IsNullOrWhiteSpace(cfg.ReadDb))
{
if (_session.TryReadByte(cfg.ReadDb, out var rb))
Runtime.ReadSignal = PlcStationLogic.ConvertRead(rb);
rt.ReadSignal = PlcStationLogic.ConvertRead(rb);
else
{
MarkDisconnected("读地址失败");
return;
MarkDisconnected($"{rt.DisplayName} 读地址失败");
return false;
}
}
if (!string.IsNullOrWhiteSpace(cfg.WriteDb))
if (string.IsNullOrWhiteSpace(cfg.WriteDb))
return true;
if (!_session.TryReadByte(cfg.WriteDb, out var wb))
{
if (_session.TryReadByte(cfg.WriteDb, out var wb))
{
Runtime.ReadWriteSignal = PlcStationLogic.ConvertWrite(wb);
if (Runtime.ReadWriteSignal == Runtime.WriteSignal)
Runtime.WriteSuccess = true;
}
else
{
MarkDisconnected("写地址回读失败");
return;
}
if (Runtime.WriteSignal != Runtime.ReadWriteSignal && !Runtime.WriteSuccess)
{
Diagnosis.Log(
$"AGV→机构 {cfg.JgName} 写入【{Runtime.WriteSignal}】请求进入{Runtime.RequestInAgvNo} 到达{Runtime.InAgvNo}",
"JGControl", true);
_session.TryWriteByte(cfg.WriteDb, (byte)Runtime.WriteSignal);
}
MarkDisconnected($"{rt.DisplayName} 写地址回读失败");
return false;
}
Runtime.IsConnected = true;
Runtime.LastError = "";
PlcStationLogic.AutoLeave(Runtime);
rt.ReadWriteSignal = PlcStationLogic.ConvertWrite(wb);
if (rt.ReadWriteSignal == rt.WriteSignal)
rt.WriteSuccess = true;
if (rt.WriteSignal != rt.ReadWriteSignal && !rt.WriteSuccess)
{
Diagnosis.Log(
$"AGV→机构 {rt.DisplayName} 写入【{rt.WriteSignal}】请求进入{rt.RequestInAgvNo} 到达{rt.InAgvNo}",
"JGControl", true);
_session.TryWriteByte(cfg.WriteDb, (byte)rt.WriteSignal);
}
return true;
}
private static void CollectBytes(PlcStationDockModel dock, List<int> bytes)
{
if (dock == null) return;
bytes.Add(dock.AllowInByte);
bytes.Add(dock.AllowOutByte);
bytes.Add(dock.EnteringByte);
bytes.Add(dock.ArrivedByte);
bytes.Add(dock.LeavingByte);
bytes.Add(dock.LeftByte);
}
private static SignalWriteValue DecodeWrite(byte[] buffer, int origin, PlcStationDockModel dock)
{
if (PlcAddress.GetBit(buffer, origin, dock.LeftByte, dock.LeftBit))
return SignalWriteValue.;
if (PlcAddress.GetBit(buffer, origin, dock.LeavingByte, dock.LeavingBit))
return SignalWriteValue.;
if (PlcAddress.GetBit(buffer, origin, dock.ArrivedByte, dock.ArrivedBit))
return SignalWriteValue.;
if (PlcAddress.GetBit(buffer, origin, dock.EnteringByte, dock.EnteringBit))
return SignalWriteValue.;
return SignalWriteValue.;
}
private static void EncodeWrite(
byte[] buffer,
int origin,
PlcStationDockModel dock,
SignalWriteValue value,
HashSet<int> changedBytes)
{
void Set(int abs, int bit, bool on)
{
var before = PlcAddress.GetBit(buffer, origin, abs, bit);
if (before == on) return;
PlcAddress.SetBit(buffer, origin, abs, bit, on);
changedBytes.Add(abs);
}
Set(dock.EnteringByte, dock.EnteringBit, value == SignalWriteValue.);
Set(dock.ArrivedByte, dock.ArrivedBit, value == SignalWriteValue.);
Set(dock.LeavingByte, dock.LeavingBit, value == SignalWriteValue.);
Set(dock.LeftByte, dock.LeftBit, value == SignalWriteValue.);
}
private void MarkDisconnected(string reason)
{
Runtime.IsConnected = false;
Runtime.LastError = reason;
LogFail($"{Runtime.Config.JgName} {reason}");
foreach (var d in _docks)
{
d.IsConnected = false;
d.LastError = reason;
}
LogFail($"{_station.JgName} {reason}");
}
/// <summary>同一机构失败日志最少间隔 5 秒。</summary>
private void LogFail(string msg)
{
if ((DateTime.Now - _lastFailLog).TotalSeconds < 5) return;
if ((DateTime.Now - _lastFailLog).TotalSeconds < 5)
return;
_lastFailLog = DateTime.Now;
Diagnosis.Log(msg, "PLC", true);
}